Phone
WhatsApp
Email
Oil Immersed Distribution transformer 10kV/35kV Electric Furnace Transformer

10kV/35kV Electric Furnace Transformer

Rated voltage10-35kv
Rated capacity4000-16000kva
Application scenariosIt is mainly used in the smelting of corundum, silica sand, calcium carbide, sulfur, graphitization, welding flux, cast steel, ceramsite sand, perlite, metallurgical auxiliary materials, carbon ferromanganese, aluminum ferromanganese, ferrovanadium, vanadium aluminum, silicon manganese alloys, etc.
Certifications & StandardsTÜV -issued CE • CB IEC EN ISO 9001• 14001• 45001

Overview

Electric furnace transformers are  mainly  used  in  resistance furnaces  and  salt  bath furnaces for  heat treatment of mechanical parts, powder metallurgy sintering, nonferrou  metal smelting, etc. , and can  also  be  used  as  power  transformers  for  steel    making  electric  arc  furnaces. The  capacity  of  electric  furnace  transformers  is  configured  according  to  the  size  of  the  electric  arc furnace  and the smelting  process. It  meets  the  requirements  of  the  smelting  process  by  means  of  voltage  regulation.

There  are  two  types  of  voltage   regulation:on-load  voltage   regulation  and   non-excitation  voltage   regulation. Large-scale electric  furnace  transformers  with  on-load  voltage  regulation  do  not  have  series  reactors, and  small  and  medium-sized electric furnace  transformers without  excitation  voltage  regulation  can  be  divided  into  two  types  with  series  reactors  and those without  reactors. The  former  relies  on  the  input  and  removal  of  the  series  reactor  to  change  the  impedance. The  latter changes  the winding  impedance  by  changing  the  connection  method  of  the  high-voltage  winding  of  the  furnace  transformer itself.

Electric furnace transformers are specialized transformers designed based on the working principles, load characteristics, and operating features of various electric furnaces. Specifically, they include transformers for various AC electric furnaces such as steelmaking electric arc furnaces, ladle refining furnaces, electroslag furnaces, submerged arc furnaces, and power frequency furnaces, as well as transformers for DC electric furnaces such as medium-frequency induction furnaces, silicon carbide furnaces, and graphitization furnaces.

Industrial electric furnace transformers are mainly divided into three categories: resistance furnace transformers, electric arc furnace transformers, and induction furnace transformers.

 

Furnace transformer parameter table
Rated
Capacity
(kVA)
Vector 
Group
Primary
Voltage
(kV)
Secondary Voltage
(V)
No. 
of 
Taps
Secondary 
Rated 
Current (A)
4000
Dd0
Yd11
10
240; 138; 121; 210
4
9630
4000
35
240; 139; 121; 210
4
9626
4200
10
240; 138; 129; 224; 210; 121
6
10112
4200
35
240; 138; 129; 224; 210; 121
6
10107
5000
10
240; 139; 121; 210
4
12028
5000
35
240; 130; 121; 210
4
12032
5500
10
260; 150; 139; 240; 210; 121
6
12208
5500
35
260; 150; 139; 240; 210; 121
6
12218
6300
10
260; 150; 139; 240; 210; 121
6
13983
6300
35
260; 150; 139; 240; 210; 121
6
13991
8000
10
260; 150; 139; 240; 210; 121
6
17749
8000
35
260; 150; 139; 240; 210; 121
6
17759
9000
Dd0
10
280; 260; 240; 220; 200; 180; 160; 140
8
18576
9000
10
290; 270; 250; 230; 210; 190; 170; 150
8
22603
9000
10
340; 320; 300; 280; 260; 240; 220; 200
8
18591
9000
Yd11
35
280; 260; 240; 220; 200; 180; 160; 140
8
18551
9000
35
290; 270; 250; 230; 210; 190; 170; 150
8
22629
9000
35
340; 320; 300; 280; 260; 240; 220; 200
8
18579
10000
Dd0
10
280; 260; 240; 220; 200; 1880; 160; 140
8
20620
10000
10
280; 260; 240; 220; 200; 1880; 160; 140
8
26228
10000
10
350; 340; 330; 320; 311; 301; 291; 280; 270
9
18539
10000
Yd11
35
280; 260; 240; 220; 200; 1880; 160; 140
8
20612
10000
35
280; 260; 240; 220; 200; 1880; 160; 140
8
26245
10000
35
350; 340; 330; 320; 311; 301; 291; 280; 270
9
18571
12500
Dd0
10
300; 290; 281; 270; 260; 250; 241; 230; 221
9
24022
12500
10
320; 298; 279; 262; 247; 233; 221; 210; 199
9
29177
12500
10
349; 328; 309; 292; 277; 263; 251; 240; 299
9
26071
12500
Yd11
35
300; 290; 281; 270; 260; 250; 241; 231; 220
9
24048
12500
35
320; 298; 278; 261; 246; 233; 221; 210; 200
9
29286
12500
35
350; 329; 310; 293; 278; 264; 252; 241; 230
9
25982
15000
Dd0
10
330; 308; 289; 272; 257; 244; 232; 221; 211
9
26228
15000
10
340; 318; 299; 282; 267; 254; 241; 230; 220
9
32414
15000
10
379; 357; 338; 319; 302; 287; 273; 261; 249
9
28800
15000
Yd11
35
330; 309; 289; 272; 257; 244; 232; 221; 211
9
26214
15000
35
340; 318; 299; 283; 268; 254; 242; 231; 221
9
32357
15000
35
380; 357; 337; 319; 302; 288; 274; 262; 251
9
28653
16000
Dd0
10
340; 318; 299; 282; 267; 254; 241; 230; 220
9
27185
16000
10
340; 318; 299; 282; 267; 254; 241; 230; 220
9
34575
16000
10
390; 365; 343; 324; 307; 290; 275; 261; 249
9
30138
16000
Yd11
35
340; 318; 299; 283; 268; 254; 242; 231; 221
9
27200
16000
35
390; 365; 342; 323; 306; 289; 275; 261; 249
9
30237
16000
35
400; 373; 350; 330; 312; 295; 281; 267; 255
9
29649

(Other specifications can be customized)

 

Type description

Related Content

Case

 

Request for Question